PSS EVE0105 A-(en) VAC D300 15
Additional Inputs / Outputs:
Two binary outputs
(limit signals) - Code S
(Options for electronics family AI 638 per EC- Certificate of
conformity PTB 00 ATEX 2128)
Stroke / angle derived from positioner feedback
2 galvanically separated limit signals
Signaling of limit value violation of the measured valve
position.
Limit signals / alarms freely configurable via local keys or
communication.
Two-wire system, according to DIN 19234, for external
supply.
supply voltage ...........DC8...36V
1) 2)
Logic:
limit value not exceeded ...<1mA
limit value exceeded......>2.2mA(typ.6mA)
device fault ............<50µA
configurable as switch output:
limit value not exceeded ...<50µA
limit value exceeded......>20mA/20V/>40mA/10V
(power derated)
Reference: AB1 for upper, AB2 for lower limit
Terminals for AB1 ........A:81+
B: 82–
AB2.........C:83+
D: 84–
Electrical classification hereto:
(Electronics family AI 638 per Certificate of Conformity
PTB 00 ATEX 2128)
see Certificate of Conformity EX EVE0105 A
TypeAI638P...........II2GEExiaIICT6
Types of protection and temperature classes as basic device.
For use in hazardous areas in circuits certified as intrinsic-
ally safe with the following maximum values:
Ui= 16 V, Ii= 80 mA, Pi= 250 mW
Internal capacitance and inductance: Ci= 26 nF, Li= 5 µH
The electric circuits of "2 binary outputs" are galvanically
separated from all other circuits and from ground.
Type of protection FM “intrinsic safety”
Class I, Div. 1, Groups A, B, C, D;
hazardous locations indoor and outdoor, NEMA Type 4X *)
Type of protection FM “non-incendive”
Class I, Div. 2, Groups A, B, C, D, F, G;
hazardous locations indoor and outdoor, NEMA Type 4X
Type of protection CSA “intrinsic safety” *)
Class I, Div. 1, Groups A, B, C, D;
hazardous locations indoor and outdoor, NEMA Type 4X *)
*) Under development
1) Other values in hazardous areas
2) On request we can specify higher voltage limits
Additional Inputs / Outputs:
Position feedback 4...20 mA – Code 4/20
(Options for electronics family AI 638 per EC- Certificate of
conformity PTB 00 ATEX 2128)
Stroke / angle derived from positioner feedback
1 output analog, galvanically separated, two-wire system
according to DIN 19234, for external supply
supplyvoltage .........DC8...36V
1) 2)
signalrange...........3.8to21.5mA
0 % and 100 % configurable
devicefault............<1mA
TerminalsforAI1 .......C:31+
D: 32–
1 binary alarm output, galvanically separated, two-wire
system, according to DIN 19234, for external supply
supplyvoltage .........external,DC8...36V
1) 2)
Logic ................noalarm...<1mA
alarm.....>2.2mA
device fault < 50 µA
TerminalsforAB1.......A:81+
B: 82–
The binary output for Alarm will be activated in the following
cases:
- Remaining control deviation
- Circuit to I/P module is disturbed
- Circuit to potentiometer is disturbed
- Calibration error:
- no angle calibration
- no current calibration
- Autostart failed
These pre-settings can be configured via communication
1)
.
Electrical classification hereto:
(Electronics family AI 638 per Certificate of Conformity
PTB00ATEX2128)
see Certificate of Conformity EX EVE0105 A
TypeAI6380Q..........II2GEExiaIICT6
Types of protection and temperature classes as basic device.
For use in hazardous areas in circuits certified as intrinsic-
ally safe with the following maximum values:
Ui= 16 V, Ii= 80 mA, Pi= 250 mW
Internal capacitance and inductance: Ci= 26 nF, Li= 5 µH
The electric circuits of "Position feedback 4...20 mA" are
galvanically separated from all other circuits and from. ground.
Type of protection FM “intrinsic safety”
Class I, Div. 1, Groups A, B, C, D;
hazardous locations indoor and outdoor, NEMA Type 4X *)
Type of protection FM “non-incendive”
Class I, Div. 2, Groups A, B, C, D, F, G;
hazardous locations indoor and outdoor, NEMA Type 4X
Type of protection CSA “intrinsic safety”
Class I, Div. 1, Groups A, B, C, D;
hazardous locations indoor and outdoor, NEMA Type 4X *)