FUNCTIONAL SPECIFICATIONS (common data for versions “Intelligent with
communication” HART, PROFIBUS-PA, FOUNDATION Fieldbus H1, FoxCom)
Features
Automatic start-up .......This function will
automatically determine the mechanical end positions of
the valve, the IP parameters, and action of the actuator
spring and the control parameters. The control parameters
are optimized dynamically during this procedure. In this
procedure, an accurate adjustment will optimize actuator
performance without additional manual settings.
Short autostart ........Automaticdetermination of the
mechanical end positions of the valve (initial value and final
value), IP parameters, action of the actuator spring,
without changing the control parameters.
Options
• Built-in independent inductive limit switches
• Pressure sensors for monitoring of air supply and out-
put pressure I (y1)
• Additional inputs / outputs:
• Position feedback 4-20 mA + binary alarm output
• 2 binary outputs (position alarms)
• 2 binary inputs
Operation and Configuration
• Simple configuration by means of 3 local push buttons,
with multilingual menu-driven graphic LCD, or LED.1)
The LCD contains three different menu languages.
Standard menu languages:
- English - German
Freely selectable third language:
- French - Portuguese - Spanish
- Italian - Swedish - ...
(further menu languages on request)
The third menu language has to be selected and specified
with the order, otherwise standard: French.
The third, freely selectable menu language can be modified
to another language by means of the configuration software
PC20/PC50.
1) Not with version FoxCom
2) With the versions “Intelligent without communication” this is only
possible with modem EDC82
3) By means of “Additional inputs / outputs”
Position feedback and Alarms
Positionfeedback.........viacommunication
Optional
3)
.............4-20mAPositionfeedback
Alarms.................viacommunication
Optional
3)
.............1Alarmoutput
Positions-Alarms .........viacommunication,
Upper and lower pre-alarm
Upper and lower main alarm
Optional
3)
.............2binaryoutputs,
Upper and lower pre-alarm
Upper and lower main alarm
Independant feedback
Limit signal switch (inductiv) . Normal version
Security version etc.
Diagnostics
–inthefield
• Self diagnostics
• Status and Diagnostic messages
• determines number of cycles, movements of actuator
– via communication and in the field
• shows condition of device:
- Potentiometer
- exceeding range of actuator (possible indication for wear
of plug or seat)
- remaining control deviation (possible indication for jam-
med actuator, blocked valve stem or plug, not sufficient
air capacity /supply air pressure /positioning pressure)
• if equipped with pressure sensors (optional):
• surveillance of air supply and output pressure,
each with display of physical value
• Additional diagnostical possibilities in control operation
by means of external sensors (optional).
Service plug and IrCom
All basic devices (except FoxCom version) are equipped with
a service plug. There via RS232 interface a PC with PC20 /
PC50 (FDT-Software) can be connected via modem EDC82
(galv. separated, not Ex).
If the D300 is equipped with option “IrCom”, communication
can take place contactless via infrared with the positioner
(even with a closed cover!). Modem “IR Interface” (not Ex)
is connected via RS232 interface to a PC (for practical
reasons a notebook) with software PC20 / PC50 (FDT soft-
ware) and makes possible a range of approx. 1 m.
(If the notebook has an IrDa interface, this cannot be used,
despite similar technique. The IrDa instruction set has no
communication commands for positioners.-)