DE3-12
DE3
CIRCUIT BREAKERS
01/15
DE3-12
QO™ and QOU Miniature Circuit Breakers
QO™ Circuit Breaker Accessories
Accessories for Use with QO™ and QOB Miniature Circuit Breakers
Handle Attachments Description Cat. No.
Handle Tie:
Conv erts any two adjacent 120/240 Vac 1P QO circuit breakers to independent trip 2P QO1HT
Conv erts any two adjacent 120/240 Vac 1P side-by-side QOT circuit breakers to independent trip 2P QOTHT
Handle tie and lock-off for three 1P QO, QOB circuit breakers QO3HT
Handle Clamp:
Clamp for holding QO 1P handle in ON or OFF position QO1LO
Clamp for holding QO or Q1 1P, 2P or 3P circuit breaker handles in ON or OFF position HLO1
Handle Padlock Attachment: for
P
adloc
king in ON or OFF position
For padlocking 1P QO circuit breaker in ON or OFF position
Loose attachment QOHPL
Fixed attachment QO1PA
For padlocking 1P side-by-side QOT circuit breaker in ON or OFF position QOTHPA
For padlocking 2P and 3P QO-GFI, QO-EPD, and QO-EPE in either ON or OFF position, fixed attachment. GFI2PA
For 2P and 3P QO and Q1 standard circuit breakers which require padlocking in either ON or OFF position.
Loose attachment QO1HPL
Fixed attachment QO1PL
Handle Padlock Attachment: for
P
adlocking in OFF position
For padlocking 1P QO circuit breaker in OFF position only, fixed attachment. QO1PAF
For padlocking 2P and 3P QO circuit breakers in OFF position only, fixed attachment. QO2PAF
For padlocking 1P QO-GFI, QO-AFI, QO-CAFI, and QO-EPD circuit breakers in OFF position only, fixed attachment. QOGFI1PAF
For padlocking 2P and 3P QO-GFI, QO-EPD, and QO-EPE circuit breakers in OFF position only, fixed attachment. QOGFI2PAF
Sub-Feed Lugs 60 A 2P plug-on
–
2 spaces required (6–2 Al/Cu) QO60SL
125 A 2P plug-on –
2 spaces required (12–2/0 Al/Cu) QO2125SL
225 A 2P plug-on –
4 spaces required (4–300 Al/Cu) QO2225SLa
125 A 3P plug-on –
3 spaces required (12–2/0 Al/Cu) QO3125SL
Mechanical Interlock Attachment
For interlocking the handles of two 2P or one 2P and one 1P QO and Q1 circuit breakers mounted side-by-side so that only one circuit
breaker
can be ON at a time (Not QOU)
QO2DTI
With Retaining Kit:
QO2DTI mechanical interlock attachment with retaining kits for securing two adjacent back-fed circuit breakers in dual power supply
applications.
Can be used with (2) 2Ps or (1) 2P and (1) 1P QO circuit breakers in QO816L100 load centers.
QO2DTIM
a Not suitable for use in 3Ø panels. Use only in 1Ø panel rated 150 A or greater.
Factory-Installed Accessories for Use with QO and QOB Miniature Circuit Breakers
Factory-installed electrical accessories take up an additional pole space on QO™, QO-GFI, QO-EPD, QO-SWN and
QOU circuit breakers. All AC electrical accessories shown below are rated for 50/60 Hz. Accessories are not available
for QOB-VH (2P 150 A and 3P 110–150 A) circuit breakers or QO, QOU molded case switches. QO circuit breakers will
accept only one accessory per circuit breaker. Undervoltage trip is not available on miniature circuit breakers. Factory-
installed accessories are not available for QO-AFI or QO-CAFI Arc Fault Circuit Breakers or on QO2150, QO2175, or
QO2200 circuit breakers.
Factory-Installed Accessories
Accessory Description
Rated
Voltage
Coil
Burden
Cat. No.
Suffix
Accessory Description
Contact
Comb.
Max.
Voltage
Max.
Load
Cat. No.
Suffix
Shunt Trip
Trips the circuit breaker from a remote
location b
y means of a trip coil
energized from a separate circuit. A
120 Vac shunt trip will operate at 55%
or more of rated voltage . All other shunt
trips will operate at 75% or more of
rated voltage.
Application
• For use with momentary or
maintained push button.
• Not available on QO-GFI, QO-
EPD, QO-AFI, QOCAFI.
• Shunt trip terminals accept
(2) 14–12 AWG Cu.
AC/DC
12 60 VA
-1042
Auxiliary
Switches
Monitors circuit breaker contact status and
provides
a remote signal indicating the circuit
breaker contacts are OPEN or CLOSED.
Application
• Auxiliary switch terminals accept
(2) 14–12 AWG Cu leads.
1A
1B
AC 120
AC 120
5A
5A
-1200
-1201
24 168 V A
AC
120 72 V A
-1021208 228 V A
240 288 V A
Alarm Switches
Used with control circuits and is actuated only
when
the
circuit breaker has tripped. Standard
construction includes a normally-open contact.
Application
• Alarm switch terminals accept
(2) 14–12 AWG Cu leads.
1A A C 120 5A -2100
Class 1130 / Refer to Catalog 0730CT9801
DE3_p012.fm Page 12 Saturday, January 10, 2015 2:13 AM