DE3
CIRCUIT BREAKERS
01/15
DE3-5
Selection Information
Molded Case Circuit Breakers
Po werPact 250 A Q-Frame P owerPact 600 A L-Frame
Circuit Breaker Type QB QD QG QJ LD LG LJ LL LR
Number of Poles 2, 3 2, 3 2, 3 2, 3 3, 4 3, 4 3, 4 3, 4 3, 4
Current Range 70–250b 70–250b 70–250b 70–250b 70–600 70–600 70–600 70–600
70–600
Interrupting Ratings
UL/CSA/NOM
Rating
(kA RMS)
(50/60 Hz)
240 Vac 10 25 65 100 25 65 100 125 200
480Y/277 Vac 18 35 65 100 200
480 Vac 18 35 65 100 200
600Y/347 Vac 14 18 25 50 100
600 Vac 14 18 25 50 100
DC Ratings
250 Vdci
500 Vdcci
IEC Rating
(kA RMS)
Icu/lcsd
240 Vac 10/5 10/5 10/5 10/5 25/25 65/65 100/100 125/125 125/125
415 Vac 10/5 10/5 10/5 10/5 18/18 35/35 65/65 100/100
100/100
Special Ratings
CCC X X X X X
Fed. Specs W -C-375B/GEN X X X X
HACR (2P, 3P) X X X X X X X
X
Connections/Terminations
Unit Mount X X X X X X X X X
I-Line™ X X X X X X X X X
Rear Connection X X X X X
Draw out X X X X X
Optional Lugs X X X X
X
Accessories and Modifications
Shunt Trip X X X X X
Undervoltage Trip X X X X X
Auxiliary Switches X X X X X
Alarm Switch X X X X X
Motor Operator X X X X X
Handle Operators X X X X X
Mechanical Interlocks (3P) X X X X X X X X X
Handle Padlock Attachment X X X X X X X X X
Cylinder Lock (3Pf)
Optional GF Protectione X X X X
X
Trip System Type
Thermal-magnetic X X X X
Instantaneous-only (MCP) X X X X X
Molded Case Switch (Automatic) X X X X
Electronic X X X X
X
Enclosures (Pages DE3-56–DE3-58)
General Purpose (NEMA 1) X X X X
Raintight (NEMA 3R) X X X X
Dust-tight (NEMA 12)
W atertight (NEMA 4, 4X, 5)
Explosion Proof (NEMA 7, 9)
Dimensions
(3P
Unit
Mount)
in. (mm)
Height 6.47 (164) 13.38 (340)
Width 4.5 (114) 5.51 (140)
Depth 3.93 (100) 4.33 (110)
Pages (Unit Mount)/(I-Line) Pages DE3-24/Section DE5 P ages DE3-25/DE3-33
Note: All circuit breakers on this chart are UL Listed and CSA Certified unless otherwise noted.
a 2P
in a 3P module.
b I-Line Q-frame circuit breakers are available 70–225 A only. 250 A Q-frame unit-mount circuit breakers are limited to Cu conductors only.
c Ungrounded UPS
systems only. See page DE3-35. Special DC J-Frame only.
d Dual CSA/UL and IEC ratings and CE markings on circuit breakers.
e Requires factory-installed
“G” shunt trip and 3P module.
f Factory-installed option
only.
g 3P only.
h 70–250 A
with electronic trip system.
i Not available with electronic trip units.
Class 500, 600, 800
DE3_p05.fm Page 5 Saturday, January 10, 2015 2:07 AM