DE3
CIRCUIT BREAKERS
01/15
DE3-5
Selection Information
Molded Case Circuit Breakers
Po werPact 250 A Q-Frame P owerPact 600 A L-Frame
Circuit Breaker Type QB QD QG QJ LD LG LJ LL LR
Number of Poles 2, 3 2, 3 2, 3 2, 3 3, 4 3, 4 3, 4 3, 4 3, 4
Current Range 70–250b 70–250b 70–250b 70–250b 70–600 70–600 70–600 70–600
70–600
Interrupting Ratings
UL/CSA/NOM
Rating
(kA RMS)
(50/60 Hz)
240 Vac 10 25 65 100 25 65 100 125 200
480Y/277 Vac — — — — 18 35 65 100 200
480 Vac — — — — 18 35 65 100 200
600Y/347 Vac — — — — 14 18 25 50 100
600 Vac — — — — 14 18 25 50 100
DC Ratings
250 Vdci — — — — — — — — —
500 Vdcci — — — — — — — — —
IEC Rating
(kA RMS)
Icu/lcsd
240 Vac 10/5 10/5 10/5 10/5 25/25 65/65 100/100 125/125 125/125
415 Vac 10/5 10/5 10/5 10/5 18/18 35/35 65/65 100/100
100/100
Special Ratings
CCC — — — — X X X X X
Fed. Specs W -C-375B/GEN X X X X — — — — —
HACR (2P, 3P) X X X — X X X X
X
Connections/Terminations
Unit Mount X X X X X X X X X
I-Line™ X X X X X X X X X
Rear Connection — — — — X X X X X
Draw out — — — — X X X X X
Optional Lugs — — — — X X X X
X
Accessories and Modifications
Shunt Trip — — — — X X X X X
Undervoltage Trip — — — — X X X X X
Auxiliary Switches — — — — X X X X X
Alarm Switch — — — — X X X X X
Motor Operator — — — — X X X X X
Handle Operators — — — — X X X X X
Mechanical Interlocks (3P) X X X X X X X X X
Handle Padlock Attachment X X X X X X X X X
Cylinder Lock (3Pf) — — — — — — — — —
Optional GF Protectione — — — — X X X X
X
Trip System Type
Thermal-magnetic X X X X — — — — —
Instantaneous-only (MCP) — — — — X X X X X
Molded Case Switch (Automatic) X — — — — X — X X
Electronic — — — — X X X X
X
Enclosures (Pages DE3-56–DE3-58)
General Purpose (NEMA 1) X X X X — — — — —
Raintight (NEMA 3R) X X X X — — — — —
Dust-tight (NEMA 12) — — — — — — — — —
W atertight (NEMA 4, 4X, 5) — — — — — — — — —
Explosion Proof (NEMA 7, 9) — — — — — — — — —
Dimensions
(3P
Unit
Mount)
in. (mm)
Height 6.47 (164) 13.38 (340)
Width 4.5 (114) 5.51 (140)
Depth 3.93 (100) 4.33 (110)
Pages (Unit Mount)/(I-Line) Pages DE3-24/Section DE5 P ages DE3-25/DE3-33
Note: All circuit breakers on this chart are UL Listed and CSA Certified unless otherwise noted.
a 2P
in a 3P module.
b I-Line Q-frame circuit breakers are available 70–225 A only. 250 A Q-frame unit-mount circuit breakers are limited to Cu conductors only.
c Ungrounded UPS
systems only. See page DE3-35. Special DC J-Frame only.
d Dual CSA/UL and IEC ratings and CE markings on circuit breakers.
e Requires factory-installed
“G” shunt trip and 3P module.
f Factory-installed option
only.
g 3P only.
h 70–250 A
with electronic trip system.
i Not available with electronic trip units.
Class 500, 600, 800
DE3_p05.fm Page 5 Saturday, January 10, 2015 2:07 AM