DE3
CIRCUIT BREAKERS
01/15
DE3-24
PowerPact™ Circuit Breaker
Q-Frame Circuit Breakers
PO WERPA CT Q-framea—250 A, Thermal-magnetic Circuit Breaker (240 Vac)
Ampere
Rating
A C Magnetic
Trip Settings
B Interrupting D Interrupting G Interrupting J Interrupting ✭
Terminal Wire
Range
■
Hold T rip
Catalogue
Number
Catalogue
Number
Catalogue
Number
Catalogue
Number
2-pole, 240 V ac
70 1000 1800
QBL22070 QDL22070 QGL22070 QJL22070
#4 AWG - 300 kcmil
Al/Cu
80 1000 1800
QBL22080 QDL22080 QGL22080 QJL22080
90 1000 1800
QBL22090 QDL22090 QGL22090 QJL22090
100 1200 2400
QBL22100 QDL22100 QGL22100 QJL22100
110 1200 2400
QBL22110 QDL22110 QGL22110 QJL22110
125 1200 2400
QBL22125 QDL22125 QGL22125 QJL22125
150 1200 2400
QBL22150 QDL22150 QGL22150 QJL22150
175 1200 2400
QBL22175 QDL22175 QGL22175 QJL22175
200 1200 2400
QBL22200 QDL22200 QGL22200 QJL22200
225 1200 2400
QBL22225 QDL22225 QGL22225 QJL22225
250 1200 2400
QBL22250■ QDL22250■ QGL22250■ QJL22250■
3-pole, 240 V ac
70 1000 1800
QBL32070 QDL32070 QGL32070 QJL32070
#4 AWG - 300 kcmil
Al/Cu
80 1000 1800
QBL32080 QDL32080 QGL32080 QJL32080
90 1000 1800
QBL32090 QDL32090 QGL32090 QJL32090
100 1200 2400
QBL32100 QDL32100 QGL32100 QJL32100
110 1200 2400
QBL32110 QDL32110 QGL32110 QJL32110
125 1200 2400
QBL32125 QDL32125 QGL32125 QJL32125
150 1200 2400
QBL32150 QDL32150 QGL32150 QJL32150
175 1200 2400
QBL32175 QDL32175 QGL32175 QJL32175
200 1200 2400
QBL32200 QDL32200 QGL32200 QJL32200
225 1200 2400
QBL32225 QDL32225 QGL32225 QJL32225
250 1200 2400
QBL32250■ QDL32250■ QGL32250■ QJL32250■
▲ Replacement lugs and electrical accessories are not available for POWERPACT Q-frame circuit breakers.
■ 250 A lugs are suitable for copper conductors only.
– Refer to Catalogue 0734CT0201 for details.
Q-Frame Termination Options
Termination Letter
A = I-Line (See Section 5)
QGL32200
For factory-installed termination,
place termination letter in the
third block of the circuit breaker
catalog number.
Termination Letter
E = Bolt-on I-Line (See Section 5)
F = No lugs
L = Lugs both ends
M = Lugs ON end, studs on OFF end
P = Lugs OFF end, studs on ON end
– Add TS suffix for studs on both ends without nuts and washers. See Catalogue
0734CT0201 for additional
information.
Q-Frame Interrupting Ratings (kA)
Voltage QB QD QG QJ
240 V 10 25 65
100✭
480 V ... ... ... ...
600 V ... ... ... ...
✭ 3-pole QJ circuit breakers are rated at 208Y/120 Vac only.
Dimensions DE3-55
Enclosures DE3-56
Class 0734 / Refer to Catalogs: 0734CT0201
DE3_p024.fm Page 24 Saturday, January 10, 2015 2:25 AM