DE3
CIRCUIT BREAKERS
01/15
DE3-50
Masterpact Universal Power Circuit Breakers
Masterpact NT/NW Circuit Breakers
Masterpact NT
Masterpact NW
The Masterpact universal power circuit breaker offers a family of circuit protection products
meeting the most common world standards, ANSI, CSA/UL and IEC. The basic design
platform for each is common. The final result is CSA/UL, ANSI and IEC circuit breakers with
the same basic external dimensions, features and accessories.
Full-Featured Performance
Complete product offering
Circuit breakers tested to show arc flash hazard risk category as referenced by NFPA70E
800 A to 6000 A frames, fixed and draw-out
Rated for AC voltage systems through 600 V (635 V ANSI)
Short-time withstand ratings up to 100 kA
Cradle position indicator: connected, test and disconnected
Simple, visual contact wear indicators
Full complement of field-installable accessories common to all standards
Four interchangeable Micrologic trip units to choose from
Available PowerLogic™ based power metering and monitoring capabilities
Available protective relay functions as defined by ANSI C37.2 and C37.90
The following charts show the Masterpact NW and NT ratings for ANSI and CSA/UL 489.
For details, please refer to Catalog 0613CT0001.
Masterpact NW Circuit Breaker Ratings
Standard ANSI C37 Certified/UL 1066 Listed UL 489 Listed
Frame Rating 800–1600 A 2000 A 3200/4000 Af 4000/5000 A 800/1200/1600/2000 A 2500/3000 A 4000/5000/6000 A
Interrupting Code N1 H1 H2 H3 L1g L1Fg H1 H2 H3 L1g L1Fg H1 H2 H3 L1g H2 H3 L1g N H Lg LFg H Lg H Lg
Interrupting Current
(kA RMS) 50/60 Hz
240 Vac 42 65 85 100 200 200 65 85 100 200 200 65 85 100 200 85 100 200 65 100 200 200 100 200 100 200
480 Vac 42 65 85 100 200 200 65 85 100 200 200 65 85 100 200 85 100 200 65 100 150 150 100 150 100 150
600 Vac 42 65 85 85 130 130 65 85 85 130 130 65 85 85 130 85 85 130 50 85 100 100 85 100 85 100
Short-time Withstand Current (kA RMS) 42 65 85 85 30 22 65 85 85 30 22 65 85 85 100 85 85 100 42a 65a 30ab 22 65 65 85 100
Built-in Instantaneous Override
(kA RMS ±10%)
c c c 85 35c 24 85 35 24 85 117
117 40 40 35ab 24 65 65 75 75
Close and latch rating (kA RMS) 42 65 40 40 25 22 65 40 40 25 22 65 40 40 40 85 75 40 40 40 25d 22 40 40 40 40
Tested to show the arc flash hazard risk
category as referenced by NFPA70E
Ye s Yes Ye s
Breaking time 25–30 ms with no intentional delay (9 ms for L1, L1F, L and LF)
Closing time 70 ms
Sensor Rating
100–250 A
400–800 A
800–1600 A
1000–2000 A 1600–3200 A
2000–4000 A
2500–5000 A
100–250 A
400–800 A
600–1200 A
800–1600 A
1000–2000 A
1200–2500 A
1600–3000 A
2000–4000 A
2500–5000 A
3000–6000 A
Endurance Rating (C/O Cycles)
With No Maintenance
Mechanical 12,500 10,000 10,000 5k 5,000 12,500e 10,000 5,000
Electrical 2800 1,000 1,000 1k 1,000 2800e 1,000 1,000
a 24
kA RMS for 800 A circuit breaker frame with 100 A or 250 A sensor.
b 65 kA RMS for 2000 A.
c None except
24 kA RMS for 800 A circuit breaker frame with 100 A or 250 A sensor.
d 40 kA RMS for 2000 A.
e The endurance rating for 2000 A, N/H/L/LF is 10,000 for mechanical and 1000 for electrical.
f 4000 A standard width circuit breaker is not available in L1 interrupting rating code or drawout construction (fixed mounting only).
g Drawout mounted
only.
Masterpact NT Circuit Breaker Ratings
Standard ANSI C37 Certified/UL 1066 Listed UL 489 Listed
Frame Rating 800 A 800 A 1200 A 1600 Ah
Interrupting Code N1 N H L1 L LFi N H L1 L LFi N H L1 L
Interrupting Current
(kA RMS) 50/60 Hz
240 Vac 42 50 65 100 200 200 50 65 100 200 200 50 65 100 200
480 Vac 42 50 50 65 100 100 50 50 65 100 100 50 50 65 100
600 Vac 35 50 35 50 35 50 N/A N/A
Short-time Withstand Current (kA RMS) 42 35 35 10 10 10 35 35 10 10 10 35 35 10 10
Built-in Instantaneous Override (kA RMS ±10%) 40 40 10 10 10 40 40 10 10 10 40 40 10 10
Close and latch rating (kA RMS) 40 25 25 10 10 10 25 25 10 10 10 25 25 10 10
Tested to show the arc flash hazard risk
category as referenced by NFPA70E
Ye s Ye s
Breaking time 25–30 ms with no intentional delay 25–30 ms with no intentional delay (9 ms for L and LF)
Closing time <50ms
Sensor Rating
100–250 A 100–250 A 600–1200 A
800–1600 A
400–800 A 400–800 A
Endurance Rating (C/O Cycles)
With No Maintenance
Mechanical 12,500 12,500
12,500 12,500
Electrical 2800 2800 2800 2800
h Fixed-mounted
only.
i Drawout mounted
only.
Masterpact NW/NT Circuit Breaker Remote Racking
Description Cat. No.
Masterpact NW/NT Remote Racking Devicesj NWNTMPRRT
Masterpact NW Remote Racking Devicej NWMPRRT
Masterpact NT Remote Rackign Devicej NTMPRRT
Mounting Bracket Kit for NW Remote Racking (contains 10 mounting brackets)k S47100
Mounting Bracket Kit for NT Remove Racking (contains 10 mounting brackets)k S47104
Control Unit for NW Remote Rackingk S47101
30 ft Control Cable for NW Remote Rackingk S47102
Drive Shaft for NW Remote Rackingk S47103
Drive Shaft for NT Remote Rackingk S47105
j Unit
comes with 10 mounting brackets included.
k For replacement only.
NWMPRRT
Class 613 / Refer to Catalog 0613CT0001
DE3_p050.fm Page 50 Saturday, January 10, 2015 2:46 AM