DE3
CIRCUIT BREAKERS
01/15
DE3-3
Selection Information
Miniature Circuit Breakers
QOU
Circuit Breakers
QOM1 and QOM2 Main
Circuit Breakers
Multi 9™ Circuit Breakers and
Supplementary Protectors
EDB Circuit Breakers
Circuit
Breaker
Type
Plug-on
Bolt-on QOM1-VH QOM2-VH EDB EGB EJB
Unit Mount QOU
CSA C22.2 No. 5/UL
489 C60
CSA
C22.2 No. 235/UL1077
C60
C60H-DCa
Number of Poles 1 2 3 2 2 1 2 3 1 2 3,4 1 2 1 2, 3 1 2, 3 1 2, 3
Current Range
10–100
10–125
10–100
50–125
100–225
0.5–35
0.5–35
0.5–35
0.5–63
1–63
1–63
0.5–40
0.5–40
15–70
15–125$
15–70
15–125$
15–70
15–125$
Interrupting Ratings
UL/CSA
Rating
(kA RMS)
(50/60 Hz)
120 Vac 10 10 10 22 22 10 10 10 10 25 25 65 65 100 100
120/240 Vac 10 10 10 22 22 5 10 10 10 10 10 18 25 35 65 65 100
240 Vac 10 5 10 10 10 10 10 18 25 35 65 65 100
277 Vac 5 5 5 18 18 35 35 65 65
377 Vac 14 18 25
480Y/277 Vac 10 10 10 5 5 18 35 65
600Y/347 Vac
14 18 25
DC Ratings
48 Vdc 5b 5b 5b 10 10 5 5
60 Vdc 5c 5c 5c 10 10 5 5
65 Vdc 10 10 5 5
125 Vdc 10 10 5 5
250 Vdc 5 5
500 Vdc 5
IEC 60947-2
(50/60 Hz)
Icu
240 Vac 20 20 20 10 10 10 20 10 20
415 Vac 10 10 5 5 10
Special Ratings
CCC Xh Xh Xh
Fed. Specs
W-C-375B/GEN
X X X X X X X X X X X X X X
Other Standard HACR d
HACR
Accessories and Modifications
Shunt Trip Xe Xe Xe X e X X X X X X X X X e X e X e X e X e X e
Undervoltage Trip X X X X X X X X
Auxiliary Switches Xe Xe Xe X X X X X X X X Xe Xe Xe Xe Xe Xe
Alarm Switch Xe Xe Xe X X X X X X X X Xe Xe Xe Xe Xe Xe
Handle Operators X X X X X X X X
Handle Padlock
Attachment
X X X
X X X X X X X X X X X X X X X X
Trip System Type
Thermal-magnetic X X X X X X X X X X X X X X X X X X X
Molded Case Switch X X
Dimensions (1P Unit Mount)
Dimensions
(1P Unit
Mount)
in. (mm)
Height 4.05 (103) 5.09 (129)f 5.60 (142)f 4.21 (107)g 3.19 (81) 3.19 (81) 5.66 (144)
Width 0.75 (19) 5.00 (127)f 5.07 (129)f 0.71 (18) 0.71 (18) 0.71 (18) 1.42 (36) 0.98 (25)
Depth 2.92 (74) 3.47 (88)f 3.60 (91)f 2.76 (70) 2.76 (70) 2.56 (65) 4.05 (103)
Pages P ages DE3-14 Section DE1 Pages DE3-16 through DE3-19 Section DE5
Note: All circuit breakers on this chart are UL Listed and CSA Certified unless otherwise noted.
a C60H-DC
is a UL 1077 (not CSA certified) supplementary protector.
b 1P and 2P, 10–70 A and 3P 10–60 A only.
c QOU is CSA/UL Listed for 60 Vdc per pole 80–100 A, 1P; 80–125 A, 2P; and 70–100 A, 3P.
d HACR on
QOU 1P and 3P 15–100 A, 2P 15–125 A;
e Factory-installed option
only
f QOM1 and
QOM2 dimensions are for 2-pole unit.
g 480 V C60 height is 5.56 in. (141 mm).
h 15–70 A
1P and 2P, 15–60 A 3P.
i 110 A maximum at 600Y/347 Vac
Class 500, 600