CIRCUIT BREAKERS
01/15
DE3-65
Moulded Case Circuit Breakers
CDP Breaker Cross to Square D
CDP Connector Kits
The CDP connector kits are used to install Square D breakers into existing Federal Pioneer CDP panels and Switchboard distribution interiors that originally
used branch breakers from the Horizon family.
Please note that these connector kits are designed to be applied on CDP interiors with Extruded Bus only, (except HDCMH, JDCMH, and LDCMH that can be
also
used on CDP interiors with Flat Bus).
Please refer to installation bulletins for detailed information on these kits.
Retrofitting or adding new Square D Breakers into CDP Interiors
Federal Pioneer
Horizon Breaker
Amperage Alternate Square D Breaker Connector Mounting Hardware
CE Breaker
15A 100A 15A 100A Powerpact H HDCMH
150A 250A 150A 225A Powerpact J JDCMH
CJL Breaker 100A 400A LA/LH LACMH
CJM Breaker* 300A 600A
400A-600A PowerPact L
LDCMH
CK 250A 1200A Powerpact P PCDPCMH
Need to be replaced in pairs, can not mount a CE breaker back to back with a PowerPact breaker. Not suitable for 100% rated and type HR, JR
MCCBs.
Available only as single mount option. Not available as a double mount or Back to back mount due to dimensional constraints.
Condition 1: Panel with all single row branch circuits.
A minimum branch circuit height of 8-1/4” is required.
Condition 2: Panel with all double row branch circuits.
This will require a modification to the trim to remove a section of the trim centre strip in the location where the new breaker is to be installed.
A minimum branch circuit height of 9-5/8” is required and the breaker should be located where the centre strip ends. (This space includes
one 1 -3/8” wide filler to suppor t the center strip).
If the breaker must be located between two sections of a double row trim then the minimum branch circuit height required is 11”. (This space
includes two 1-3/8” wide fillers to support both ends of the centre strips)
The PowerPact L-Frame breaker has an overall height of 5-1/2” but will be fitted with a Cover plate to fill the existing branch circuit space of
8-1/4”.
Available only for single mount. The CK breaker can not be replaced in existing 12X of branch circuit height, the Square D PowerPact breaker
requires space with a 16X branch nominal height. Contact Schneider Services for installation of PowerPact P breaker and mounting hardware.
* PowerPact L-Frame can also be used to replace Square D LC/LI/LX/LE/LXI installed in CDP panels as a replacement of CJM breakers.
DE3_p065.fm Page 65 Friday, January 23, 2015 12:24 AM