DE3
CIRCUIT BREAKERS
01/15
DE3-21
PowerPact™ Molded Case Circuit Breakers
PowerPact Family
The PowerPact Advantage
• Proven Performance: Industry-leading circuit breaker innovation and protection for heavy-duty commercial and industrial
applications.
• Smart: Integrated metering options provide a cost-effective solution to reduce energy consumption, optimize energy costs, and
improve energy availablility for your facilities.
• Flexible: Full range of thermal-magnetic and electronic trip molded case circuit breakers from 15 A to 3000 A, delivering the ratings,
configurations, and operators for your unique applications.
• Simple: Common catalog numbers, standardized ratings, and a full range of field-installable accessories make product selection,
installation and maintenance easier than ever.
• Common Design Features: Mounting holes, door trim, and handle accessories.
H-Frame
150 A
J-Frame
250 A
Q-Frame
250 A
L-Frame
600 A
M-Frame
800 A
P-Frame
1200 A
R-Frame
3000 A
PowerPact Interrupting Ratings
Voltage
Interrupting Rating
B D G J K L R
240 Vac 10 kA 25 kA 65 kA 100 kA 65 kA 125 kA 200 kA
480 Vac 18 kA 35 kA 65 kA 65 kA a 100 kA 200 kA
600 Vac 14 kA 18 kA 25 kA 65 kA a 50 kAb 100 kA
a P-frame K interrupting is 50 kA at 480 and 600 Vac.
b P-frame L
interrupting is 25 kA at 600 Vac.
Common Catalog Numbering System
Frame
Rating
Termination
Poles
Voltage
Amperage
c
Suffix
Code
Suffix
Code
H G L 3 6 1 5 0 A B S A
110 Vac Shunt Trip
2A/2B Auxiliary Switch
Frame Designation Interrupting Rating Terminations
240 Vac 480 Vac 600V ac A I-Line
H 150 A Fr ame B 10 kA L Lugs on Both Ends
J 250 A Fr ame D 25 kA 18 kA 14 kA F Bus Bar (No Lugs)
Q 250 A Fr ame G 65 kA 35 kA 18 kA M Lugs Line Side Only
L 600 A Fr ame J 100 kA 65 kA 25 kA P Lugs Load End Only
M 800 A Fr ame K 65 kA 65 kA 65 kA N Plug-in
P 1200 A Fr ame L 125 kA 100 kA 50 kA D Drawout
R 3000 A Fr ame R 200 kA 200 kA 100 kA S Rear Connected Studs
c For amperage of M-, P- or R-frame circuit breakers, add a zero to the three amperage digits; for example, 120 = 1200 A.
Description................................................Page
H- and J-Frame Circuit Breakers .............................DE3-22
H- and J-Frame Circuit Breakers .............................DE3-23
Q-F rame Circuit Breakers ...................................DE3-24
L-F rame Circuit Breakers ...................................DE3-25
P-F rame Circuit Breakers ...................................DE3-27
R-F rame Circuit Breakers ...................................DE3-28
P o werPact™ H- and J-Frame Electronic Motor Circuit Protectors ...DE3-29
Motor Circuit Protectors and Motor Protector Circuit Breakers ......DE3-31
Automatic Switches ........................................DE3-34
500 Vdc Circuit Breakers....................................DE3-35
Mission Critical Circuit Breakers ..............................DE3-37
P o werPact™ Circuit Breaker Accessories ......................DE3-39
Motor Operators and Rotary Handles .........................DE3-40
Locks, Installation Accessories, and Rear Connections ...........DE3-41
Mechanical Lugs ..........................................DE3-41
Compression Lugs and Po w er Distribution Connectors (PDC)......DE3-43
Terminal Nuts, Terminal Pads, Terminal Shields and Accessories ...DE3-44
Plug-In and Drawout Mountings ..............................DE3-45
Micrologic™ Electronic Trip Units .............................DE3-46
Micrologic™ Trip Unit Accessories ............................DE3-48
Class 611
DE3_p021.fm Page 21 Saturday, January 10, 2015 2:23 AM