CIRCUIT BREAKERS
01/15
DE3-35
500 Vdc Circuit Breakers
CSA/UL Listed 500 Vdc Circuit Breakers
CAUTION/PRECAUCION/
ATTENTION
Connect only as shown/Conectar solo asi/
Francher seulement comme suit:
300 V 300 V
Load/Carga/
Charge
600 V MAX.
MAX. MAX.
Load/Carga/
Charge
or
o
ou
Source = 600 Vdc max. (floating)
500 Vdc max. (loaded)
DC Circuit Breaker Label
The CSA/UL Listed thermal-magnetic molded case circuit breakers shown below are
specifically designed for use on ungrounded dc systems having a maximum short-circuit
voltage of 500 Vdc or a maximum floating (unloaded) voltage of 600 Vdc. The circuit
breakers are suitable for use only with UPS (uninterruptable power supplies) and
ungrounded systems.
This two-level voltage rating allows these circuit breakers to be applied to battery sources
having a short-circuit availability of 20,000 amperes for LH, and MH circuit breakers and
25,000 amperes for PAF circuit breakers at 500 Vdc.
LH and MH circuit breakers are provided with an adjustable magnetic trip that is readily
accessible by means of a single adjustment on the face of the circuit breaker. PAF circuit
breakers have a fixed magnetic trip range.
These circuit breakers are CSA/UL Listed for the interrupting ratings shown only if applied
with three poles connected in series (series connection is external to circuit breaker). See
diagram below.
NOTE: Due to external series connection, I-Line™ circuit breakers are not available for
this application.
DC Molded Case Circuit Breakers
Ampere Rating
Circuit Breaker
Cat. No.
Adjustable Magnetic Trip Range—DC
Amperesa
Interrupting Rating
@ 500 Vdc
Low High
100 A JGL37100D81 400 600
20 k AIR
125 A JGL37125D81 400 600
150 A JGL37150D81 400 600
175 A JGL37175D81 400 600
200 A JGL37200D82 500 850
20 k AIR225 A JGL37225D82 500 850
250 A JGL37250D82 500 850
250 A LHL3625025DC 625 1250
20 k AIR
300 A LHL3630026DC 750 1500
350 A LHL3635029DC 875 1750
400 A LHL3640030DC 1000 2000
450 A MHL3645031DC 1125 2250
20 k AIR
500 A MHL3650032DC 1250 2500
600 A MHL3660033DC 1500 3000
700 A MHL3670035DC 1750 3500
800 A MHL3680036DC 2000 4000
900 A MHL3690039DC 2500 5000
1000 A MHL36100040DC 2500 5000
1200 A MHL36120040DCb 2500 5000 25 k AIR
450 A MHL3645031DCH 1125 2250
50 k AIR
500 A MHL3650032DCH 1250 2500
600 A MHL3660033DCH 1500 3000
700 A MHL3670035DCH 1750 3500
800 A MHL3680036DCH 2000 4000
900 A MHL3690039DCH 2500 5000
1000 A MHL36100040DCH 2500 5000
1200 A MHL36120040DCHb 2500 5000 50 k AIR
a Magnetic
trip
tolerances are -20%/+30% from the nominal values shown.
b Suitable for
use only in a ventilated enclosure. Minimum enclosure dimensions are 38"hx20"wx7"dwith a
minimum of 300 square inches of ventilation near the top and bottom of the enclosure.
Ampere Rating
Circuit Breaker
Cat. No.
Fixed Magnetic Trip Range—DC
Amperesa
Interrupting Rating
@ 500 Vdc
Hold Trip
1200 A PAF361200DC 1200 1620
25 k AIR1600 A PAF361600DC 1600 2160
2000 A PAF362000DC 2000 2700
2500 A PCF362500DC 2500 3375 25 k AIR
Accessories .........................................
PageDE3-39
Optional Lugs .......................................P
ageDE3-42
Dimensions ..............................Pages DE3-54 and DE3-55
Enclosures..................................Pages DE3-56
DE3-58
Class 500, 600
DE3_p035.fm Page 35 Saturday, January 10, 2015 2:30 AM