DE3
CIRCUIT BREAKERS
01/15
DE3-53
Ground-Fault Protection Equipment
Add-On Ground-Fault and Earth-Leakage Modules
GFM250
Optional GFM25CT
The Micrologic ground-fault module (GFM) is a CSA certified and UL Listed circuit breaker
accessory which protects equipment from damage caused by ground faults. It is an add-on
module which, when connected to a PowerPact H- or J-frame thermal-magnetic circuit breaker
only, provides ground-fault sensing and ground-fault relay functions.
HD/JD Add-on Ground-fault Module Features:
Adjustable ground-fault pickup levels
Adjustable ground-fault time delays
Integral ground fault push-to-test feature and ground-fault indicator
All GFMs are supplied for I-Line
®
mounting, easily convertible to unit mount by removing the I-Line
brackets
Fault-powered (through the sensing current transformer) for electronics, shunt trip, and integral test
feature.
Optional neutral current transformer GFM25CT for 3-phase 4-wire applications. Refer to instructions
for proper installation
Shunt trip S29382 (12 Vdc): is required for circuit breaker. This may be factory-installed (suffix SN)
or field-installed
NOTE: Ground-fault modules cannot be used for alarming only.
Module/Enclosure Selection Chart a
Companion
Circuit Breaker
Prefix
Catalogue Number
q
Enclosure Space Required
Ground-fault
Pickup Adjustment
Range
I-Line
Switchboard
HD, HG, HJ, HL GFM150HD LA 20–100 A
JD, JG, JJ, JL GFM250JD LA 40–200 A
Accessories
H&J GFM25CT Optional Neutral Current Transformer (required for 4-wire systems)
a At 250 A, the GFM250JD can be used with 80% rated circuit breakers only.
I-Line™ J-Frame with ELM installed
Earth Leakage Module (ELM) for PowerPact H- and J-Frame MCCBs
The Earth Leakage Module (ELM) is an add-on module which, when connected to a
PowerPact H- or J-frame MCCB, provides low-level ground-fault sensing and ground-fault
relay functions.
Because these ELMs are highly sensitive (30 mA to 3 A), they provide much greater
protection than GFMs (20 Amps to 200 Amps sensitivity). The ELMs provide greater
protection of control circuits and other sensitive equipment. The associated circuit breaker
must have a 48 Vdc shunt trip, which may be field-installed (kit S29392) or factory-installed
(suffix –SP) in the H- or J-Frame circuit breaker.
Add-on Earth Leakage Module (ELM) Features:
Adjustable ground-fault pickup levels as low as 30 mA
Adjustable ground-fault time delays from instantaneous to 500 msec
(Time delay can be applied to the 30 mA setting)
Integral ground fault push-to-test feature
Ground-fault indicator (LED for local status; contacts for remote indication)
All ELMs are supplied for I-Line™ mounting and are easily convertible to unit-mount by removing the
I-Line brackets
Three poles; 240 to 600 Vac maximum: 3-wire applications only (no neutral)
Line-power obtained through internal bus to provide power for electronics, shunt trip, and integral
test feature.
A shunt trip is required in the circuit breaker; it may be field-installed or factory-installed in the
PowerPact H and J circuit breakers.
UL 1053 Ground-fault Sensing and Relaying Equipment
ELM Selection Chartb
Companion Circuit Breakerc Enclosure Space
Required I-Line
Switchboard
Pick-Up Adjustment
Range
Catalog Number
Prefix Size
HD, HG, HJ, HL 15–150 A LA 30 mA–3 A ELM150HD
JD, JG, JJ, JL 150–250 A LA 30 mA–3 A ELM250JD
b At 250 A, the ELM250JD can be used with 80% rated circuit breakers only.
c For Factory Installation of ELM Module: For termination designation (3rd letter of catalog number) use ONLY “M”.
Add
factory installed 48 Vdc shunt trip (suffix SP) to breaker plus suffix VL or VM.
Use VL for H frame.
Use VM for J frame.
Class 931, 940, 960